Product display

 

Water cooled dual cool unit(30-100kW)

Profile information:
basic information
Categories:
Dual cool unit
没有此类产品
产品描述
"

Dual cool unit

Renovo dual-cooled units equipped with two totally independent circuits they are direct expansion and chilled water. This unit is usually used where an installation has a chilled water source which the service cannot be continuously relied on. In this case function priority is given to the chilled water circuit, with the microprocessor controls when the chilled water supply fails or if the water is not cold enough to dissipate the entire heat load. Alternatively the unit can be set to priority direct expansion cooling, activating chilled water operation only in the event of a compressor malfunction. Both air-cooled and water-cooled can be applied in DX system.

 

Indoor unit Model

RDT-RUT

030A

042C

057C

064C

080D

090D

100D

Cooling capacityIndoor condition24-50%RH,water-cooled DX type

Total Capacity

kW

31.6

45.3

58.2

66.6

82.3

92.8

101.5

Sensible Capacity

kW

29.8

42.6

55.3

62.3

76.7

86.8

93.5

Cooling capacityIndoor condition24-50%RHchilled water temp:7/12

Total Capacity

kW

28.3

39.1

51.2

51.2

62.5

64.5

65.3

Sensible Capacity

kW

27.6

38.2

50.2

50.2

60.0

61.0

62.0

Cooling capacityIndoor condition24-50%RHchilled water temp:10/15

Total Capacity

kW

18.1

25.7

33.1

33.1

40.0

45.0

45.0

Sensible Capacity

kW

18.1

25.7

33.1

33.1

40.0

The next article